- Rated Voltage: 0.6/1 kV AC
- Rated DC Voltage: 1.5 kV
- Maximum Permitted DC Voltage: 1.8 kV (conductor/conductor, non earthen system, circuit not under load)
- Maximum Permitted AC Voltage: 1 kV
- Working Voltage: DC 1000 V
- Spark Test: 6000 V AC (8400 Vdc)
- Voltage Withstand: 6500 V as per EN50395 for 5 min
- Ampacity: According to requirements for cables for PV systems
- Ambient Temperature: -40°C – +90°C
- Minimum Bending Radius: 5 x OD (fixed), 15 x OD (occasional flexing)
- Flame retardant according to IEC 60332-1-2
- Low smoke emission < 20% as per ASTM D-2843
- Halogen free according to EN 50267-2-1/-2, IEC 60754-2
- Maximum Temperature at Conductor: 120°C (20000h)
- Short Circuit Temperature: 200°C (at conductor max. 5 sec)
- Thermal Endurance Test: According to EN 60216-2 (temperature index +120°C)
- High Temperature Pressure: Test according to EN 60811-3-1
- Excellent mechanical and electrical properties
- UV resistance & OZONE resistance
- Flexibility & suitability for fast & easy installation
EN 50618
Coils 100, 200, 300, 500, 1000m
Flexible Electrolytic fine Tinned copper class-5 conductor according to IEC 60228
XLPO (Crosslinked Halogen Free & Flame Retardant)
XLPO (Crosslinked Halogen Free & Flame Retardant)
Red, Black and also available black color with red lining
For Solar Panel, Solar Power Plant, Solar Pump Installation.
| Size of Cable | Max. Conductor D.C. Resistance at 20°C | Insulation Thickness | Sheath Thickness | Outer Diameter | Current Rating Under Continuous Operation 90°C and Ambient Temperature 40°C (in A) | Short Circuit Current Rating for 1 sec. Duration (in KA) |
|---|---|---|---|---|---|---|
| Sq.mm | ohm / (km) | (Nominal) mm | (Nominal) mm | mm | A | kA |
| 1.5 | 13.7 | 0.60 | 0.70 | 4.30 | 22 | 0.189 |
| 2.5 | 8.71 | 0.70 | 0.80 | 5.0 | 30 | 0.315 |
| 4.0 | 5.09 | 0.70 | 0.80 | 5.60 | 42 | 0.504 |
| 6.0 | 3.39 | 0.80 | 0.90 | 6.20 | 52 | 0.756 |
| 10.0 | 1.95 | 0.80 | 0.90 | 7.10 | 76 | 1.26 |
| 16.0 | 1.24 | 0.90 | 1.0 | 8.30 | 95 | 2.02 |
- Current Rating Conversion Factors For Different Ambient Temperature
| Ambient Temperature °C | Up to 60 | 70 | 80 | 90 |
|---|---|---|---|---|
| Conversion Factor | 1 | 0.92 | 0.84 | 0.75 |
Note: The number of wires and diameter mentioned in the table are approximate and nominal; however, they shall meet the requirements of conductor resistance as per standards. In view of continuous improvements in design and process, information, dimensions and specifications may change without notice.
Explore Rolson’s range of dependable wires and cables, designed for reliable performance across automotive, electrical, industrial, solar and specialised applications.