Products & Solutions

Harmonized Cables

Rolson Cables H05Z-K 300/500 V and H07Z-K 450/750 V

H05Z-K 300/500 V and H07Z-K 450/750 V

H05Z-K and H07Z-K harmonized cables use flexible stranded copper conductors with low-smoke, halogen-free insulation. Their flame-retardant and low-smoke properties are intended to support safer internal wiring in buildings and confined spaces.

Cable Structure

  • Conductor: Fine-stranded plain copper, Class 5, to VDE 0295 / IEC 60228
  • Insulation: Flame-retardant, low-smoke, halogen-free EI5 LSZH compound
  • Colours: Green/yellow, blue, black, brown, grey, orange, pink, red, violet, white, green, yellow or other colours
  • Flame propagation: Zero halogen IEC 60754-2 and flame-retardant test as per IEC 60332-1

Technical Data

ParameterSpecification
Operating Temperature−30°C to +90°C
Nominal VoltageH05Z-K: 300/500 V; H07Z-K: 450/750 V
Test VoltageH05Z-K: 2500 V; H07Z-K: 2500 V
Insulation ResistanceMinimum 10 MΩ × km
Minimum Bending Radius4 × cable diameter

Applications

  • Fixed installation in conduits and under plaster
  • Appliance wiring and distribution stations
  • Lamps, devices, switchgear cabinets and distribution boxes

Standard Packing

Harmonized cable source lists coils of 100 m and 200 m in carton boxes or reels for most single-core variants. The H05VV-F / H05V2V2-F page lists 100, 200, 500 and 1000 m reels.

Cable Features

  • Special heat-resistant thermosetting insulation
  • Low smoke and halogen-free construction
  • High current-carrying capacity
  • Reduced heat-energy radiation
  • High flexibility
  • Resistance to moisture, abrasion, grease and oil
  • Good mechanical and electrical properties
  • Zero-halogen test per IEC 60754-2; flame propagation test per IEC 60332-1

H05Z-K (300/500 V) — Technical Sizes

Size (mm²)Strands / Diameter (Nom.)Insulation Thickness (mm, Nom.)Outer Diameter (mm, Approx.)Max. Copper Resistance (Ω/km)
0.516/0.2000.602.1039.00
0.7524/0.2000.602.2026.00
132/0.2000.602.7019.50

H07Z-K (450/750 V) — Technical Sizes

Size (mm²)Strands / Diameter (Nom.)Insulation Thickness (mm, Nom.)Outer Diameter (mm, Approx.)Max. Copper Resistance (Ω/km)
1.530/0.2500.703.2513.30
2.550/0.2500.803.807.98
456/0.3000.804.504.95
684/0.3000.805.253.30
10140/0.3001.006.501.91
16224/0.3001.008.001.21
25350/0.3001.2010.100.780
35490/0.3001.2011.300.554
50703/0.3001.4013.500.386
70988/0.3001.4015.300.272
951349/0.3001.6018.000.206
120608/0.5001.6019.800.161
150760/0.5001.8022.300.129
185943/0.5002.0023.900.106
2401225/0.5002.2026.800.0801

Source note: conductor wire counts are approximate and wire diameters nominal; the reference states that conductor resistance should satisfy the applicable IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360 requirements.


Harmonized Standard Other Products

Explore the available harmonized cable variants below.

Download Brochure (PDF)

Explore Our Other Products

Explore Rolson’s range of dependable wires and cables for automotive, electrical, industrial, solar and specialised applications.

Reliable wires and cables for demanding applications. Discuss Your Requirement